Federal Bid

Last Updated on 06 Sep 2019 at 8 AM
Combined Synopsis/Solicitation
Location Unknown

Underground Storage Tank Repair and Inspection

Solicitation ID FA462519Q0116
Posted Date 15 Aug 2019 at 5 PM
Archive Date 06 Sep 2019 at 5 AM
NAICS Category
Product Service Code
Set Aside Total Small Business (SBA) Set-Aside (FAR 19.5)
Contracting Office Fa4625 509 Cons Cc
Agency Department Of Defense
Location United states

Response to Requested Information:
1. Does the Government pass EPA (Environmental Protection Agency) for the distance between the tanks and their respective meters? Yes
2. Can CE provide a copy of the As Builts to include tank sizes, diameter and length? No
3. How many gallons does each tank hold?

   
 

 

 

 

 

Tank ID

Air Tank ID

Tank Type

Content

Status

UST?

Volume (gal)

UST 1119-01 - HUT-02

HUT-02 - 1119-01

HFR

DIESEL FUEL

IN-SERVICE

Yes

2,500

UST 1119-02 - HUT-01

HUT-01 - 1119-02

HFR

GASOLINE

IN-SERVICE

Yes

2,500

UST 1119-03 - HUT-03

HUT-03 - 1119-03

HFR

JET A

IN-SERVICE

Yes

2,500

UST 150

UST 150

HFR

DIESEL FUEL

IN-SERVICE

Yes

2,500

 

 

 

 

 

 

 

UST 30

UST 30

HFR

DIESEL FUEL

IN-SERVICE

Yes

550

UST 33

UST 33

HFR

DIESEL FUEL

IN-SERVICE

Yes

1,000

UST 34

UST 34

HFR

DIESEL FUEL

IN-SERVICE

Yes

2,000

UST 5034-01

UST 5034-01

HFR

DIESEL FUEL

IN-SERVICE

Yes

1,000

UST 5100-01

UST 5100-01

HFR

DIESEL FUEL

IN-SERVICE

Yes

15,000

UST 7-01 - HUT-03

HUT-03 - 7-01

HFR

JET A

IN-SERVICE

Yes

2,500

UST 7-02 - HUT-03

HUT-03 - 7-02

HFR

JET A

IN-SERVICE

Yes

6,000

UST 7-03 - HUT-03

HUT-03 - 7-03

HFR

JET A

IN-SERVICE

Yes

6,000

 

 

4. Are the tanks made of steel? No, fiberglass construction
5. Do the tanks have fiberglass lining? They are made of fiberglass
6. Is the piping in the tanks and spill buckets double walled? The piping to the tank is double walled, but piping in the tank is single walled.
7. Do the tanks have inner-stitial metering? Yes
8. Does the Government keep track of what is in each tank manually (ie does the Government use a dipstick to manually track/monitor the amount of fluid in each tank). Yes
a. Does the Government inventory the amount of fluid in each tank and compare it with their respective Veeder Root data? Yes
9. How long do you run the generators for and why? Yes, for 15 minutes and 1 hour to simulate a power outage.
10. Does Veeder Root register the fuel that goes into the tanks? It monitors the levels
11. Are there lift stations? No
12. How many tanks are on the flight line? 6
13. How many tanks are in a controlled area, but not on the flight line? 1
14. How many tanks are there total? 12
15. How many tanks contain diesel fuel? 7
16. How many tanks contain Jet-A fuel? 4
17. How many tanks contain MO gas? 1

For additional information, please refer to the Department of Natural Resources website for the state of Missouri at https://dnr.mo.gov/env/hwp/tanks/docs/slade-ust-updates.pdf

 

 

Bid Protests Not Available

Similar Past Bids

Smyrna Delaware 07 Aug 2017 at 5 PM
Smyrna Delaware 02 May 2018 at 8 PM
Smyrna Delaware 07 Aug 2017 at 3 PM
Smyrna Delaware 02 May 2018 at 8 PM
Smyrna Delaware 07 Aug 2017 at 4 PM

Similar Opportunities

Fort wayne Indiana 30 Jul 2025 at 4 AM (estimated)
Tinker air force base Oklahoma 04 Apr 2026 at 4 AM
Washington navy yard District of columbia 30 Jul 2025 at 4 PM