GENERATOR PREVENTATIVE MAINTENANCE (TO BE PERFORMED EACH QUARTER) AS FOLLOWS: REPLACE ENGINE OIL FILTERS. CHANGE ENGINE OIL. INSPECT AIR FILTERS. CLEAN OR REPLACE AIR FILTERS AS NEEDED. REPLACE FUEL FILTERS OR CLEAN FUEL STRAINER AS REQUIRED. INSPECT AND CLEAN COOLING FINS. INSPECT ALL BELTS AND HOSES. INSPECT, TEST & SERVICE BATTERIES, CABLES AND TERMINALS. CHECK AND ADJUST CHARGING SYSTEM. CHECK STARTER AND STARTING SYSTEM. REPLACE SPARK PLUGS AS REQUIRED. INSPECT, CLEAN, ADJUST AND LUBRICATE THE GENERATOR AS REQUIRED. INSPECT, CLEAN, TEST AND ADJUST THE TRANSFER SWITCH. TEST AND EXERCISE SYSTEM AND RESET TO OWNERS SCHEDULE. START AND RUN SYSTEM. TRANSFER LOAD TO SYSTEM WITH CUSTOMERS AUTHORIZATION. PROVIDE A WRITTEN REPORT ON THE CONDITION OF THE SYSTEM. PROVIDE WARRANTY ON ALL WORK AND MATERIALS FOR A MINIMUM OF 30 DAYS FROM DATE OF SERVICE AND/OR REPAIR. OVERTIME LABOR FOR A TECHNICIAN/JOURNEYMAN (OVERTIME IS CONSIDERED ANY TIME NOT COVERED UNDER NORMAL WORKING HOURS) ESTIMATED HOURS: 100