Fire Alarm & Sprinkler Test/Inspection Service
Oklahoma City VA Health Care System
VA Medical Center
Oklahoma City, OK. 73104
BRIEF SCOPE OF WORK
(This is for information only)
Fire Alarm & Sprinkler Testing & Inspection Services in accordance with the terms and conditions stated within this abbreviated Performance Work Statement (PWS).
The subsequent solicitation is planned to be a Base with Four possible Option Year(s) Contract.
This is a Request for Information (RFI) Only for Market Research purposes, no Award will be made from this RFI.
The subsequent Contract will be a Base with Four possible Option Year(s) Contract, funded by FY21 appropriations, with a start date on or after 1 October 2020.
Oklahoma City VA Medical Center is seeking a qualified contractor to provide Testing & Inspection services of Fire Alarm & Sprinkler System at the main VA hospital facility and Lawton CBOC, in accordance with the most current edition of The National Fire Protection Association s (NFPA) Code.
Contractor to supply all labor, materials, and other supplies needed to complete all tasks in accordance with most current edition of NFPA 72 and NFPA 25: Provide all necessary trained and qualified personnel, labor, equipment and calibration instruments to perform preventive maintenance and inspections for the Government-owned Fire Protection Systems specified herein. The systems include fire alarm systems and sprinklers and all peripherals associated with these systems including, but not limited to:
1. Test all alarm initiating devices such as manual pull stations, heat detectors, smoke detectors, air duct smoke detectors and fire sprinkler water flow switches.
2. Test all supervisory initiating devices such as fire sprinkler valves and low air switches.
3. Test all audible and visual alarm devices.
4. Perform all control unit tests such as output control functions (i.e. fan shut-down, door control, elevator capture, etc.) battery charging circuit tests, initiating and indicating circuit supervision, magnetic locking devices and ground detection.
5. Prepare and submit a detailed test report indicating each device tested, type of test for each device, the test result for each device and each device's location. Joint Commission format and need report before payment received.
6. Prepare and submit a detailed deficiency list indicating the problems found and code references where applicable.
1) FIRE ALARM SYSTEMS Testing to include annual November, semi-annual May, and quarterly November, February, May, August testing.
a) Inspections: The vendor shall inspect to ensure that the systems, in their entirety, are operating at their optimum. The vendor shall make all inspections in accordance with the manufacturer s standard practice, instructions and current NFPA 72: National Fire Alarm Code.
b) Testing: The vendor shall perform all tests as required by either the manufacturer or contained in current NFPA 72: National Fire Alarm Code, i.e. pull stations, heat and smoke detectors, signaling circuits and all other initiating, signaling and monitoring devices requiring testing.
2) FIRE SPRINKLER SYSTEMS Testing to include annual, semi-annual, and quarterly testing.
a) The vendor shall provide all necessary trained and qualified personnel, labor, and equipment to inspect, and test the fixed automatic fire sprinkler systems and equipment located in Buildings in accordance with NFPA 25: Inspection, Testing & Maintenance of Water Based Fire Protection Systems.
The system components and quantities are described below.
The testing of these systems will include the following items on the following schedule (or updated schedule specified in latest versions of NFPA 72 and NFPA 25):
VA Medical Center Oklahoma City
System
Component
Testing
Number of items
Fire System
Supervisory Signals
Quarterly
7
Fire System
Off Site Notification (DACT)
Quarterly
1
Fire System
Duct Detectors
Annual
76
Fire System
Heat Detectors
Annual
50
Fire System
Smoke Detectors
Annual
403
Fire System
Pull Boxes
Annual
188
Fire System
Electronic Releasing Devices
Annual
118
Fire System
Audio/Visual Devices (as listed below)
Annual
Fire System
Horn Only
0
Fire System
Horn Strobe
0
Fire System
Strobe Only
325
Fire System
Speaker Strobe
303
Fire System
Speaker Only
644
Fire System
Emergency Service Notification
Annual
1
Fire System
AHU Shutdown
Annual
73
Fire System
Annunciators
Annual
5
Fire System
Power Supplies
Annual
24
Fire System
Door Holder
Annual
118
Fire System
Digital Alarm Comm Transmitter
Annual
1
Fire System
FACP Panel
Annual
26
Fire System
BAT Batteries
Annual
42
Fire System
PWRS Power Supply
Annual
24
Fire System
Elevator
Annual
12
Fire System
Elevator Primary Recall Test
Annual
12
Fire System
Elevator Alternate Recall Test
Annual
12
Fire System
Elevator Shunt Trip
Annual
12
Fire System
Roll down fire curtains
Annual
2
Fire System
Fire doors connected to security system
Annual
4
Fire System
Battery Charging Circuits
Annual
24
Sprinkler System
Main Drains
Quarterly
3
Sprinkler System
Fire Department Connections
Quarterly
ÃÂ 5
Sprinkler System
Tamper Switches
Semi-Annual
114
Sprinkler System
Water Flows
Semi-Annual
93
Sprinkler System
Backflow Preventers (one in a confined space)
Annual
ÃÂ 4
Sprinkler System
Hydrant
Annual
ÃÂ 1
Sprinkler Systems
Wet Systems
Annual
5
Sprinkler Systems
Dry Systems
Annual
1
Sprinkler Systems
Control Valves
Annual
124
Sprinkler System
Standpipe - Flow Test
5-year (last completed 3/2016; due 3/2021)
ÃÂ 1
Lawton Outpatient
System
Component
Testing / Date
Number of items
Fire System
Supervisory Signals
Quarterly
2
Fire System
Off Site Notification (DACT)
Quarterly
1
Fire System
Duct Detectors
Annual
5
Fire System
Heat Detectors
Annual
2
Fire System
Smoke Detectors
Annual
45
Fire System
Pull Boxes
Annual
14
Fire System
Electronic Releasing Devices
Annual
Fire System
Audio/Visual Devices (as listed below)
Annual
46
Fire System
Horn Only
Fire System
Horn Strobe
Fire System
Strobe Only
Fire System
Speaker Strobe
Fire System
Speaker Only
Fire System
Emergency Service Notification
Annual
1
Fire System
AHU Shutdown
Annual
5
Fire System
Annunciators
Annual
1
Fire System
Power Supplies
Annual
1
Fire System
Door Holder
Annual
4
Fire System
Digital Alarm Comm Transmitter
Annual
1
Fire System
FACP Panel
Annual
1
Fire System
BAT Batteries
Annual
4
Fire System
PWRS Power Supply
Annual
1
Fire System
Elevator
Annual
Fire System
Elevator Primary Recall Test
Annual
Fire System
Elevator Alternate Recall Test
Annual
Fire System
Elevator Shunt Trip
Annual
Fire System
Roll down fire curtains
Annual
Fire System
Fire doors connected to security system
Annual
Fire System
Battery Charging Circuits
Annual
Sprinkler System
Main Drains
Quarterly
1
Sprinkler System
Fire Department Connections
Quarterly
Sprinkler System
Tamper Switches
Semi-Annual
2
Sprinkler System
Water Flows
Semi-Annual
1
Sprinkler System
Backflow Preventers (one in a confined space)
Annual
1
Sprinkler System
Hydrant
Annual
1
Sprinkler Systems
Wet Systems
Annual
1
Sprinkler Systems
Dry Systems
Annual
1
Sprinkler Systems
Control Valves
Annual
3
Sprinkler System
Standpipe - Flow Test
5-year (last completed 3/2016; due 3/2021)
1
Locations of performance
Oklahoma City VA Health Care System
VA Medical Center
921 NE 13th St
Oklahoma City OK 73104
Lawton VA Outpatient Clinic (CBOC)
4303 Pitman St
Lawton OK 73503
IMPORTANTR NOTE: This RFI (Request for Information) is for information only.
No award will be made from this RFI.
Please communicate via e-mail to
[email protected] by COB June 24, 2020 as to your company s ability to perform service per this brief Scope of Work.
If interested, please provide the following:
Please state your company s business size
Please provide DUNS number
If you have a FSS/GSA contract that includes this service
Provide FSS/GSA contract number if applicable
Bid Protests Not Available