Revised Vendor Q & A - RFQ 36C24721Q1050 - BASELINE ASBESTOS INSPECTION How many buildings are included in the SOW? One building Can you provide a list of the Building Numbers included in the SOW? Main Hospital - VAMC/Bldg 1 109 Bee St., Charleston, SC 29401 How many floors are there for each building? The main hospital VAMC/Bldg #1 has five floors and a crawl space. What is the square footage for each building? 513,255 sf Do Homogeneous Areas that are not positive for Asbestos need to be photographed and included in the Final Report? Yes, included but only need positive photos on the drawings of page it is taken with corresponding sample #, negatives can be elsewhere in report with sample #. Are photographs required for each sample or just each Homogeneous Area? Each sample Where are per sample costs to be entered on the Price/Cost Schedule response? Please provide your total cost under CLIN 0001 (BASELINE ASBESTOS FACILITY INSPECTION TO INCLUDE BULK SAMPLING, ANALYSIS, SUMMARY REPORT (DRAWINGS/PHOTOS) AND LABELING POSTITVE ACM) as required in the RFQ. Approximately 297 homogeneous materials with up to 1000 PLM and 297 TEM What level of Asbestos is considered Asbestos Containing Material and by what Analytical Method(s)? Asbestos-containing material (ACM)Â means any material containing more than 1% asbestos. Analytical method is identification by polarized light microscopy (PLM), phase contrast microscopy (PCM), and transmission electron microscopy (TEM). We will accept stop positives.