Complete natural gas burner assembly as described below. The burner fuel and air inlets shall be pre-plumbed assemblies with necessary fittings for operation. Associated fuel trains and blowers will be included for each burner assembly, as well as local control panels. A calibration of the burners will be provided by the vendor after the government has completed install.
ThermJet 0750 Model Burner (After Burner System PRJ101029536 Eclipse - no substitution)
•7,500,000 Btu/hr •Ambient temperature, no preheat •High velocity outlet•Alloy tube combustor•Natural gas fuel•UV scanner adapter
Each burner will have an associated compatible blower and air manifold assembly included.
•Blowers will include associated silencer/filter
•Pre-piped air manifold assembly includes: properly sized nipple flange; modulating butterfly valve with 4-20mA I/O; and associated purge switch, combustion switch, pressure gauge, and cock valve.
Each burner above will have its own skidded fuel/valve train.
•1.5 in NPT Main•NEMA 4•Siemens SSOVs•Pressure Switches•Junction Box •Skid orientation to be confirmed with Government•Blowers will have associated silencer/filters
Each burner will have a gas burner manifold assembly to include the associated: •Ratio Regulator•Limiting Gas Valve•Flex Nipple/Union
Provide NEMA Type 4 control panel for each burner. Does not require a PID controller, as that will be handled through PLC. Items included for each burner assembly: •UV Scanner •Terminal Transformer •Ignition Transformer • Wire, 16 AWG Ignition, High Temp •4-20 mA outputs on controls, to connect to the site's PLC
Calibration: A calibration of the burners will take place at MCAAP, Oklahoma after government install.Complete natural gas burner assembly as described below. The burner fuel and air inlets shall be pre-plumbed assemblies with necessary fittings for operation. Associated fuel trains and blowers will be included for each burner assembly, as well as local control panels. A calibration of the burners will be provided by the vendor after the government has completed install.
ThermJet 0500 Model Burner (Retort Burner System PRJ101029534 Eclipse - no substitution)
•5,000,000 Btu/hr •Ambient temperature, no preheat •High velocity outlet•Alloy tube combustor•Natural gas fuel•UV scanner adapter
Each burner will have an associated compatible blower and air manifold assembly included.
•Blowers will include associated silencer/filter
•Pre-piped air manifold assembly includes: properly sized nipple flange; modulating butterfly valve with 4-20mA I/O; and associated purge switch, combustion switch, pressure gauge, and cock valve.
Each burner above will have its own skidded fuel/valve train.
•1.5 in NPT Main•NEMA 4•Siemens SSOVs•Pressure Switches•Junction Box •Skid orientation to be confirmed with Government•Blowers will have associated silencer/filters
Each burner will have a gas burner manifold assembly to include the associated: •Ratio Regulator•Limiting Gas Valve•Flex Nipple/Union
Provide NEMA Type 4 control panel for each burner. Does not require a PID controller, as that will be handled through PLC. Items included for each burner assembly: •UV Scanner •Terminal Transformer •Ignition Transformer • Wire, 16 AWG Ignition, High Temp •4-20 mA outputs on controls, to connect to the site's PLC
Calibration: A calibration of the burners will take place at MCAAP, Oklahoma after government install.